Wire Size Calculator

A wire size calculator finds the smallest copper AWG whose circular mils exceed 2 × 12.9 × feet × amps ÷ (volts × drop). 120 V, 20 A, 100 ft at 3% needs 8 AWG.

Minimum copper wire size8 AWG
Actual drop at that size2.60%
Size set byvoltage drop
Required circular mils14333
Total length
Length along a straight run. Enter the total distance to cover.

Wire size calculator: the smallest copper gauge for your run

A wire size calculator works backwards from the voltage drop you will accept. It computes how many circular mils of copper the circuit needs, then picks the smallest standard American Wire Gauge (AWG) that has at least that much. For a 120 V, 20 A load 100 feet away with a 3 percent drop limit, the answer is 8 AWG.

Conductor sizing is safety-critical and governed by code. Confirm the final choice with a licensed electrician and your local code before wiring.

The formula in plain words

Wire pushes back against current, and the longer and thinner it is, the harder it pushes. That push eats voltage before it reaches the load. You decide how much you can lose, and the formula tells you how fat the wire must be.

  • Allowed drop in volts = voltage × max drop %
  • Required circular mils = (2 × 12.9 × one-way feet × amps) ÷ allowed drop
  • Pick the smallest gauge whose circular mils are at least that number

The 12.9 is a resistivity constant for copper. The 2 covers the round trip.

Worked examples

  1. 120 V, 20 A load, 100 ft one-way, 3% max drop
  • Allowed drop: 120 × 0.03 = 3.6 V
  • Required: (2 × 12.9 × 100 × 20) ÷ 3.6 = 14,333 CM
  • 10 AWG has 10,380 CM, which is too small. 8 AWG has 16,510 CM, which works.
  • Actual drop at 8 AWG: 2.60 percent
  1. 240 V, 50 A load, 150 ft one-way, 3% max drop
  • Allowed drop: 240 × 0.03 = 7.2 V
  • Required: (2 × 12.9 × 150 × 50) ÷ 7.2 = 26,875 CM
  • 6 AWG has 26,240 CM, just 635 short. The pick is 4 AWG (41,740 CM).
  • Actual drop at 4 AWG: 1.93 percent

In example 2, 6 AWG misses by only about 2 percent, and the calculator still bumps you up to 4 AWG.

Results for 120 V, 20 A, 3% limit

One-way length Required CM Calculator pick Drop at that gauge
25 ft 3,583 12 AWG 1.65%
50 ft 7,167 10 AWG 2.07%
100 ft 14,333 8 AWG 2.60%
150 ft 21,500 6 AWG 2.46%
200 ft 28,667 4 AWG 2.06%

In the 25 ft row, voltage drop alone would allow 14 AWG, but 14 AWG copper is only good for 15 A, so the calculator returns 12 AWG and shows “Size set by: ampacity”. On the longer rows, voltage drop sets the size.

How to gather the inputs

  • Voltage: Use the supply voltage at the panel, such as 120 or 240.
  • Current: Use the load’s running amps. For a continuous load, ask your electrician about derating.
  • Length: Measure the cable path, not the straight line. Include vertical runs and detours.
  • Max drop: Start at 3 percent. Lower it for long runs to sensitive equipment.

Common mistakes

  • Ignoring the breaker size. The calculator sizes the wire for the load current you enter. If the breaker is larger than the load, size the wire for the breaker instead.
  • Entering the round-trip length. The formula already doubles it.
  • Sizing aluminum with copper numbers. Aluminum needs a larger gauge.
  • Ignoring temperature and bundling. Wire in hot attics or crowded conduit carries less current than the nameplate number.
  • Rounding down. If the required circular mils land between two gauges, you must take the larger conductor.

Where this calculator stops

The tool checks one thing: voltage drop for steady current. It does not account for conductor temperature, bundled cables in one conduit, or the brief surge a motor draws when it starts, which can be several times its running current.

A common planning guide splits the allowance, with about 3 percent on a branch circuit and 5 percent on the whole path from service to load. If a feeder already eats part of that budget, set a lower limit here. Then have the final gauge checked against code.

After choosing a gauge, check it with the voltage drop calculator, confirm the breaker with the breaker size calculator, and see whether the cables fit your raceway using the conduit fill calculator.

Embed this calculator on your site

Free to use. Paste this into your page's HTML. Please keep the link under the calculator.

Frequently asked questions

How is wire size chosen?

Two things set the minimum: the circuit's ampacity (the current the wire can safely carry) and voltage drop over distance. This calculator checks both. It finds the smallest copper gauge that keeps drop under your limit, compares it with the smallest gauge that can carry the current, and gives you the thicker of the two.

What max voltage drop should I use?

3 percent is the commonly recommended limit for a branch circuit and a safe default. Use 2 percent for sensitive electronics or very long runs. The same 120 V, 20 A, 100 ft run needs 8 AWG at 3 percent but 6 AWG at 2 percent.

Does a lower AWG number mean thicker wire?

Yes. The AWG scale runs backwards. 14 AWG is thin, 12 is thicker, and the numbers keep dropping to 1, then 1/0 (entered as 0 here) and larger. Thicker wire has more circular mils and less voltage drop.

Is this ampacity or voltage-drop sizing?

Both. For short runs ampacity usually governs: 20 A needs at least 12 AWG copper no matter how short the run. For long runs, voltage drop pushes you to a thicker wire than ampacity alone would. The calculator picks the larger of the two and shows which one set the size. Ampacity uses the 60 °C column of NEC Table 310.16; your installation may allow a higher column.

What about aluminum wire?

This calculator sizes copper. Aluminum carries less current per gauge and drops more voltage, so an aluminum run typically needs to be one or two sizes larger. Have an electrician confirm aluminum sizing.

Why is the run length one-way?

You enter the distance from the panel to the load. The formula multiplies by 2 inside it to account for the current traveling out and back, so entering the round-trip length would double-count the distance.

Estimates only. Verify quantities with your supplier before purchasing.